  • Temperature and humidity transmitter BT1H-3A

  • Suitable for pipeline monitoring, central air conditioning, telecommunications base stations, grain storage, precision computer rooms, electronics industry, archive storage, textile industry

Product Manual

Product Specification Book

  • Product Name:

    Pipeline temperature and humidity transmitter

    Product model:

    BT1H-3A

    Version:

    V1.0

    Formulator:

    He Genwen

    Reviewer:

    Yuan Chao

     

    1. Application areas:

    Suitable for pipeline monitoring, central air conditioning, telecommunications base stations, grain storage, precision computer rooms, electronics industry, archive storage, and textile industry.

     

    2. Detection method:

    Connect the transmitter according to the wiring diagram and turn on the power supply  DC24V, Insert the transmitter probe into the constant temperature and humidity chamber and conduct a comparison test according to the temperature and humidity control table below.

    Table 1 Temperature output current value

    -20

    -10

    0

    10

    20

    30

    40

    50

    60

    70

    80

    Output(mA)

    4

    5.6

    7.2

    8.8

    10.4

    12

    13.6

    15.2

    16.8

    18.4

    20

    Table 2 Humidity output current value (T=23℃)

    %RH

    20

    30

    40

    50

    60

    70

    80

    90

    Output(mA)

    7.2

    8.8

    10.4

    12

    13.6

    15.2

    16.8

    18.4

     

    3. Performance indicators:

     Humidity sensitive components: imported humidity sensitive capacitors

     Temperature sensitive components:  Pt1000

     Supply voltage: AC/DC  24V±20%

     Use temperature range: -25 ~85℃

     Temperature detection range: -20 ~80℃

     Humidity detection range: 0 ~100%RH

     Output method: three-wire system, 4-20 mA

     Storage temperature range: -10 ~40℃

     Storage humidity range: 30 ~70%RH

     Humidity detection accuracy: ±3%RH (Temperature 23 ℃, Humidity 30%-90% )  Temperature detection accuracy: ±0.3℃

     Load impedance: ≤500 Ω

     Resurgence:  IEC61000-4-5   Level 3

     

    4. Installation diagram:

    Wiring diagram:

     

    5. Notes:

     Please strictly follow the wiring diagram. If the wrong wiring may cause damage to the transmitter;

      Installed in places with better ventilation or air flow;

      Avoid strong vibrations.


  • Home
  • Product Display
  • Qualification certificate
  • Application News
  • Consulting
  • phone:0755-26588758 13714285279(倪先生) 13922884770(王先生) 13923716479(倪先生)


    fax:0755-26747274


    email:info@source-sensor.com


    address:East 3rd Floor, Building 15, Majialong Industrial Zone, Nantou Street, Nanshan District, Shenzhen


    Copyright©2002-2023 Yuanjian Sensing Technology. All Rights Reserved Copyright 粤ICP备17008245号-5 技术支持:图页网 网站地图xml 网站地图html