Product Name: | Pipeline temperature and humidity transmitter |
Product model: | BT1H-3A |
Version: | V1.0 |
Formulator: | He Genwen |
Reviewer: | Yuan Chao |
1. Application areas:
Suitable for pipeline monitoring, central air conditioning, telecommunications base stations, grain storage, precision computer rooms, electronics industry, archive storage, and textile industry.
2. Detection method:
Connect the transmitter according to the wiring diagram and turn on the power supply DC24V, Insert the transmitter probe into the constant temperature and humidity chamber and conduct a comparison test according to the temperature and humidity control table below.
Table 1 Temperature output current value
℃ | -20 | -10 | 0 | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 |
Output(mA) | 4 | 5.6 | 7.2 | 8.8 | 10.4 | 12 | 13.6 | 15.2 | 16.8 | 18.4 | 20 |
Table 2 Humidity output current value (T=23℃)
%RH | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 |
Output(mA) | 7.2 | 8.8 | 10.4 | 12 | 13.6 | 15.2 | 16.8 | 18.4 |
3. Performance indicators:
Humidity sensitive components: imported humidity sensitive capacitors
Temperature sensitive components: Pt1000
Supply voltage: AC/DC 24V±20%
Use temperature range: -25 ~85℃
Temperature detection range: -20 ~80℃
Humidity detection range: 0 ~100%RH
Output method: three-wire system, 4-20 mA
Storage temperature range: -10 ~40℃
Storage humidity range: 30 ~70%RH
Humidity detection accuracy: ±3%RH (Temperature 23 ℃, Humidity 30%-90% )
Temperature detection accuracy: ±0.3℃
Load impedance: ≤500 Ω
Resurgence: IEC61000-4-5 Level 3
4. Installation diagram:
Wiring diagram:

5. Notes:
Please strictly follow the wiring diagram. If the wrong wiring may cause damage to the transmitter;
Installed in places with better ventilation or air flow;
Avoid strong vibrations.