  • Water immersion sensor WLS-07

  • WLS-07 The water-immersion sensor is mainly used to detect water immersion and leakage in related places.This product is collected using an electrode-type water-immersion probe, and is analyzed and processed by a high-precision microprocessor to output the corresponding switching quantity.It is widely used in computer rooms, warehouses, libraries, archives and other places that require water immersion and testing.


Product Manual

pic

Product Specification Book

  • Product Name:

    Electrode water immersion sensor

    Product model:

    WLS-07

    Version:

    V1.0

    Formulator:

    He Genwen

    Reviewer:

    Yuan Chao


    1. Scope of application:

    WLS-07 The water-immersion sensor is mainly used to detect water immersion and leakage in related places.This product is collected using an electrode-type water-immersion probe, and is analyzed and processed by a high-precision microprocessor to output the corresponding switching quantity.It is widely used in computer rooms, warehouses, libraries, archives and other places that require water immersion and testing.

     

    2. Electrical parameters:

    Operating voltage: 12 VDC (9~16VDC)

     Quiescent current: ≤30mA

     Alarm current: ≤100mA

     Working environment: -20 ~+80℃ ,10%RH~100%RH

     Storage environment: -40 ~+85℃ ,10%RH~100%RH

     Alarm output: relay NC/NO (default NC)

     Jumper settings: can set the alarm output to be normally turned on  (NO) 、Normally closed   (NC)

     Probe: Electrode type water-immersion probe

     Sensitivity: 0-50 KΩStepless adjustment

     Response time: <1S

     

    3. Line sequence definition of power supply and alarm output interface

    Serial number

    Define the signal

    Definition description

    1

    +12V

    DC power supply positive pole

    2

    GND

    DC power supply negative pole

    3

    ALARM+

    Alarm port

    4

    ALARM-

    Alarm port

     

    4. Definition of the wire sequence of the electrode type water-immersion probe interface

    Serial number

    Define the signal

    Definition description

    1

    WATER+

    Probe port

    2

    WATER-

    Probe port

     

    5. Installation method

     Host installation method: 1. Wall-mounted installation;2. Magnetic installation.

     Installation method of electrode type water-immersion probe: 1. Screw fixation installation;2. Adhesive installation;3. Installation of cable ties.


  • Home
  • Product Display
  • Qualification certificate
  • Application News
  • Consulting
  • phone:0755-26588758 13714285279(倪先生) 13922884770(王先生) 13923716479(倪先生)


    fax:0755-26747274


    email:info@source-sensor.com


    address:East 3rd Floor, Building 15, Majialong Industrial Zone, Nantou Street, Nanshan District, Shenzhen


    Copyright©2002-2023 Yuanjian Sensing Technology. All Rights Reserved Copyright 粤ICP备17008245号-5 技术支持:图页网 网站地图xml 网站地图html