  • Atmospheric pressure sensor BPS-1S

  • BPS-1S It is a high-precision atmospheric pressure data acquisition transmitter, using MODBUS Industrial control bus protocol, multiple transmitters can be connected to the network for common bus, or other compliant MODBUS RTU Protocol bus networking.This product can monitor changes in atmospheric pressure in real time and stably, and has the characteristics of small size and easy installation. The product has reliable performance, long service life and fast response speed.


Product Manual

pic

Product Specification Book

  • Product Specifications

    Product Name:

    Atmospheric pressure transmitter

    Product model:

    BPS-1S

    Version:

    V1.0

    Formulator:

    He Genwen

    Reviewer:

    Yuan Chao

     

     

     

     

    Modify the record table:

     

     

     

    Version

    Change content

    Change people

    Change date

    V1.0

    New

    He Genwen

    2020-4-24

     

    1. Product Introduction

    BPS-1S  It is a high-precision atmospheric pressure data acquisition transmitter, using MODBUS  Industrial control bus protocol, multiple transmitters can be connected to the network for common bus, or other compliant MODBUS RTU  Protocol bus networking.This product can monitor changes in atmospheric pressure in real time and stably, and has the characteristics of small size and easy installation. The product has reliable performance, long service life and fast response speed.

    2. Scope of application

     

    Widely applicable to environments where air pressure is measured, such as environmental testing, industrial testing, meteorological research, farmland measurement, wind resource assessment, etc.

    3. Technical parameters

     

    Working power supply

    DC 9V

    Output signal

    MODBUS RTU  protocol

    Range range

    300hpa-1100hpa

    Accuracy level

    0.5%FS

    Response time

    ≤1S (@25℃)

    Operating temperature

    40℃~80℃

    Storage temperature



    Installation method

    Wall hang +Magnetic suction

    Shell parameters

    ABS  White 61 X (45+18) X30mm

    weight

    34g

     

    4. Appearance and size drawing (unit: mm, Dimensional tolerance: ± 1.0mm)

     

    V. Wiring diagram

     

     Power supply positive pole  (VCC)

     RS485  Output (A)

     RS485  Output (B)

     Negative power supply  (GND)

     

    VI. Communication Protocol

     

    1.Product command sending and response speed:

    1) The instruction sending time interval is recommended to be greater than 0.5 seconds

    2) The recommended time for reading response after sending the command is greater than 0.2 seconds

    2.Agreement Overview:

    Compliance with this Agreement  MODBUS  Communication protocol, adopted MODBUS  Subsets in the protocol RTU  Way: RS485  Half-duplex Working mode.

    3.The meaning of commands and commands and data supported by skewers:

    4.Serial data format:

    1) CRC  Verification polynomial: 0 xA001

    2) Communication protocols can transmit signed shaping numbers or floating-point type data.

    3) Serial port setting: the baud rate default is 9600 bps,8  Bit data bit, 1 bit stop bit, no check bit

    4) The serial port baud rate supported by this transmitter

    It is: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

     

     

    7. Detailed explanation of communication commands:

     Read pressure value  (Integer ) :

    The command sent by the host computer: 01 04 00 00 00 01 31  CA

    The host computer received the command: 01 04 02 02 93  F8 3D

    Among them: the 4th and 5th bytes represent the received current pressure value, and its value is divided by 100 that is the current actual pressure value;

    In the above example, it is 02 93, and the decimal is 659. Divided by 100 and it is 6.59, which is the current pressure value.   Read pressure value command  (Floating point number ) :

    Please refer to the transmission of floating point numbers  MODBUS-RTU  Provisions on multi-byte floating point transmission in the protocol.Send command Tx:01 03 00 16 00 02 25 CF

    01 Slave address, 03 Function code, 00 16 Offset address, 00 02 Number of words read.

    Return data Rx:01 03 04 BE 40 E6 12 15 A2

    01 Slave address, 03 function code, 04 bytes, BE 40 E6 12  for  IEE754  floating point number.

    Pay attention to distinguishing the data division in the protocol, such as offset address 22  (10 Pricing ) ,16 The binary is expressed as 16, pay attention to distinguishing this difference.

     Read communication baud rate:

    Send command Tx:01 03 00 01 00 01 D5 CA

    Return data Rx:01 03 02 00 03 F8 45

    Among them: the 4th and 5th bytes are the high and low bits of the read communication baud rate: 00 00

     Examples of rewriting baud rate commands:

    Send command  Tx: 01 06 00 01 00 04 D9 C9

    01 Local address, 06 function code, 00 01 offset address, 00 04 rewrite baud rate is 4  (Corresponding to 19200 ) to cache.

    Return data  Rx: 01 06 00 01 00 04 D9 C9

    Query address command: Send command  Tx: 00 03 00 16 00 02 24 1E

    Return data  Rx: 02 03 04 40 16 D1 24 61 7C

    02 For the local address found, the remaining data is ignored.

     Example of rewriting address command:  (Note: After changing the address, you must execute the next save command )

    Send command  Tx:01 06 00 00 00 02 08 0B

    01 Local address, 06 function code, 00 00 offset address, 00 02 Rewrite address 2 to cache.

    Return data  Rx:01 06 00 00 00 02 08 0B

     Save address command:

    Send command  Tx:02 06 FF FF 00 00 89 DD

    02 Local address, 06 function code,  FF FF  Offset address, 00 00 Rewrite address 2 to cache.Return data Rx:02 06 FF FF 00 00 89 DD

     

    8. Things to note

     

     The product's voltage cannot exceed the rated voltage range  (9V-16V) ;

     The installation height is the height of the equipment that mainly requires environmental conditions;

     Install in a stable environment to avoid direct light and stay away from windows, air conditioners, heating and other equipment, otherwise it will cause

    Inaccurate measurement of atmospheric pressure;

     The transmitter probe part is a sensitive component, please do not rotate or remove the housing at will. Improper operation may cause measurement.

    Inaccurate quantity or even damage sensitive components.


  • Home
  • Product Display
  • Qualification certificate
  • Application News
  • Consulting
  • phone:0755-26588758 13714285279(倪先生) 13922884770(王先生) 13923716479(倪先生)


    fax:0755-26747274


    email:info@source-sensor.com


    address:East 3rd Floor, Building 15, Majialong Industrial Zone, Nantou Street, Nanshan District, Shenzhen


    Copyright©2002-2023 Yuanjian Sensing Technology. All Rights Reserved Copyright 粤ICP备17008245号-5 技术支持:图页网 网站地图xml 网站地图html